An Off-line Simulation Test and Verification System for Third-party Communication Stations of Nuclear Power Plant DCS

Authors

  • Zhaoxu Kang Liaoning Hongyanhe Nuclear Power Co., Ltd., Dalian 116300, China

DOI:

https://doi.org/10.6911/WSRJ.202611_12(11).0008

Keywords:

Distributed control system (DCS); communication station; protocol simulation; off-line verification; virtualization.

Abstract

The distributed control system (DCS) of the nuclear power plant has communication interfaces with many third-party systems, such as APA, RGL, GRE/GME, LSS, SEK and JDT. Before replacing a faulty communication station, you have to do parameter configuration, Linux installation, serial port and protocol configuration, but there is no verification window or off-line platform, so a spare station may fail to establish communication on site. Therefore, an off-line simulation test and verification system based on Python and virtualization technology is designed and implemented. The system consists of a simulation server, an engineer station, communication stations, a KVM switch and a movable cabinet. The simulation server runs CentOS and simulation software for MODBUS-TCP, IEC 60870-5-104 and MODBUS-RTU; The engineer station uses VMware to reproduce Windows XP/7 configuration environments; The station establishes a real data link with the simulation server. Application results show that the system can fully verifies link establishment, functional intact, point-value consistency before on-site deployment. What’s more, eliminating the risk of unverifiable spare stations and improving equipment reliability.

Downloads

Download data is not yet available.

References

[1] National Technical Committee on Industrial Process Measurement, Control and Automation of Standardization Administration of China. (2008). GB/T 19582.1-2008 Industrial automation networks based on Modbus protocol - Part 1: Modbus application protocol. Standards Press of China.

[2] Modbus Organization. (2006). MODBUS over serial line specification and implementation guide V1.02.

[3] International Electrotechnical Commission. (2006). IEC 60870-5-104:2006 Telecontrol equipment and systems - Part 5-104: Transmission protocols - Network access for IEC 60870-5-101 using standard transport profiles.

[4] National Energy Administration. (2009). DL/T 634.5104-2009 Telecontrol equipment and systems - Part 5-104: Transmission protocols - Network access for IEC 60870-5-101 using standard transport profiles. China Electric Power Press.

[5] Matthes, E. (2016). Python crash course: A hands-on, project-based introduction to programming. Posts & Telecom Press.

[6] VMware Inc. (n.d.). VMware Workstation Pro documentation. https://docs.vmware.com/